| Plan Review Notes For Permit 00060164 |
| Permit Number |
00060164 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED********************************** | | | SUPPLY AIR & RETURN AIR SHOWS ON PLANS | | | THAT AIR HANDLER UNIT #1, INDICATE THE | | | UNITS THAT SUPPLIES EACH AREA. | | | 2. A/C SUPPLY DROP ON AHU #2 NEEDS CFM | | | VALUE. | | | 3. INDICATE ON PLANS EXHAUST FANS SIZES, | | | DUCT SIZES IN THE BATHROOMS PER 1997 | | | SMC 503.1 | | | 4. PROVIDE THE DRYER SIZE OF THE VENT, | | | DUCT SIZE AND FAN ON PLANS. |
|