| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | SUBMIT A SANITARY RISER THAT COMPLIES W/ | | | THE STANDARD PLUMBING CODE PRIOR TO | | | INSPECTION. | | | A)WATER CLOSETS NOT PERMITTED ON WET | | | VENTS.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 911.1.1. | | | | | | B)CIRCUIT AND LOOP SYSTEM SHALL COMPLY | | | W/SPC SEC.914.1,914.2,914.3.4,920.3,IF | | | THAT IS THE INTENT OF THE DESIGN.I HAVE | | | NO IDEA WHAT YOU ARE ATTEMPTING WITH THE | | | SANITARY SYSTEM AS DRAWN. | | | | | | C)CLEARLY INDICATE ON THE PLAN WHERE | | | SANITARY RISERS #5-8 CONNECT TO RISERS | | | #1-4.COUNTYWIDE AMENDMENTS 104.2.1. | | | | | | D)CONDENSATE DRAIN SHALL BE EQUIPPED W/ | | | AN EMERGENCY OVERFLOW. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER |
|