| Plan Review Notes For Permit 00060163 |
| Permit Number |
00060163 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE ADDRESS FIRST SET OF NOTE | | | -S. PLEASE SUBMIT COMPLETED LOAD CALCU- | | | -LATIONS AND SHOW ALL CONTINUOUS LOADS | | | AND LARGEST MOTOR AT 125%. | | | 2)NOTE: PLEASE SEE 240-3-D FOR OCP | | | OF CIRCUIT #13 OF PANEL "LB" . | | | PLEASE CORRECT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|