| Plan Review Notes For Permit 00060162 |
| Permit Number |
00060162 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE FIRST SET OF NOTES!!! | | | LOAD CALCULATIONS HAVE STILL NOT BEEN | | | SUBMITTED. SEE ART;215-5 OF THE NEC. | | | PLEASE SUBMIT LOAD CALCULATIONS, LOADS | | | AT 125% FOR CONTINUOUS LOADS AND FOR | | | LARGEST MOTOR. | | | | | | 2)NOTE: PLEASE SHOW BLDG.STEEL AND COLD | | | WATER BOND FOR GROUNDING ELECTRODE | | | SYSTEM. 250-50/215-5 | | | | | | 3)NOTE: AS PER CHANGES MADE TO SHEET | | | E 2.2. PLEASE SEE FL ADMINISTRATIVE CODE | | | AND COUNTY WIDE ADMIN. CODE 104.2 AND | | | 104.2.7. PLEASE RE-DO SHEET FOR CU DISC. | | | CHANGES. | | | | | | 4)NOTE: PLEASE SEE CIRCUIT 19/21PANEL | | | "LA". SHOWS WIRE SIZE #12 W/ 25 OCP.AND | | | #10 GROUND? PLEASE CLARIFY. SEE 240-3-D | | | SEE CIRCUIT# 23/25 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL!!!!! | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|