Plan Review Notes
Plan Review Notes For Permit 00060162
Permit Number 00060162
Review Stop E
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE FIRST SET OF NOTES!!!
 LOAD CALCULATIONS HAVE STILL NOT BEEN
 SUBMITTED. SEE ART;215-5 OF THE NEC.
 PLEASE SUBMIT LOAD CALCULATIONS, LOADS
 AT 125% FOR CONTINUOUS LOADS AND FOR
 LARGEST MOTOR.
  
 2)NOTE: PLEASE SHOW BLDG.STEEL AND COLD
 WATER BOND FOR GROUNDING ELECTRODE
 SYSTEM. 250-50/215-5
  
 3)NOTE: AS PER CHANGES MADE TO SHEET
 E 2.2. PLEASE SEE FL ADMINISTRATIVE CODE
 AND COUNTY WIDE ADMIN. CODE 104.2 AND
 104.2.7. PLEASE RE-DO SHEET FOR CU DISC.
 CHANGES.
  
 4)NOTE: PLEASE SEE CIRCUIT 19/21PANEL
 "LA". SHOWS WIRE SIZE #12 W/ 25 OCP.AND
 #10 GROUND? PLEASE CLARIFY. SEE 240-3-D
 SEE CIRCUIT# 23/25
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL!!!!!
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372