| Plan Review Notes For Permit 00060162 |
| Permit Number |
00060162 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)FLOOR DRAINS W/TRAP PRIMERS ARE REQD. | | | IN THE TOILET ROOMS.SPC SEC.409.4.1.1. | | | | | | 2)SUBMIT SIGNED AND SEALED WATER RISER | | | DIAGRAM FOR ALL WORK BEING DONE. | | | | | | 3)FIXTURE P-10 NOT ON PLUMBING RISER. | | | SUBMIT SIGNED AND SEALED REVISED | | | SANITARY RISER DIAGRAM. | | | | | | 4)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SECS.4.1.3.,4.15.PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | 5)FLOORS AND WALLS IN TOILET ROOMS SHALL | | | BE NONABSORBENT TO A HEIGHT OF 4'PER SBC | | | SEC.1204.2. | | | | | | *****NOTE:I WAS GOING TO APPROVE THIS | | | PLAN W/PROVISOS BUT OTHER DISCIPLINES | | | HAVE REJECTED THE PLANS.MAKE ALL THE | | | REQUIRED PLUMBING CORRECTIONS. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|