| Plan Review Notes For Permit 00060162 |
| Permit Number |
00060162 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 2ND REVIEW | | | | | | 1] PRODUCT TEST REPORTS SUBMITED ARE NOT | | | ACCEPTABLE,CHECK REPORT NUMBERS. | | | SUBMIT TESTING FOR ROOF COVER. | | | 2] PLANS SHALL REFERENCE ASCE 7-95 SEE | | | NOTES ON S1.1. | | | 3] PROPOSED FIN. FLOOR 17.50' SHALL BE | | | REFERENCED ON THE PLANS. | | | 4] IF THE CEILING WILL BE 1/2" DRYWALL | | | PLEASE CHANGE THE DRAWINGS. | | | | | | | | | | | | | | | REVIEWED BY; | | | LUIS MARTINEZ | | | 659-8096 #8456 |
|