2001-01-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PROVIDE ONE LINE DIAGRAM OF
 RISER DIAGRAM.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATONS
 SHOWING WHERE THE TOTAL LOAD IS COMING
 FROM. PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE SHOWN/FIGURED AT 125%
 PLEASE SHOW.
  
  
 3)NOTE PLEASE NOTE THE LOCATIONS OF A/C
 C.U. DISCONNECTS. REQ`D WITHIN 6`
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. 659-8096 EXT 8372