| 2001-01-08 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PROVIDE ONE LINE DIAGRAM OF | | | RISER DIAGRAM. | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATONS | | | SHOWING WHERE THE TOTAL LOAD IS COMING | | | FROM. PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS ARE TO BE SHOWN/FIGURED AT 125% | | | PLEASE SHOW. | | | | | | | | | 3)NOTE PLEASE NOTE THE LOCATIONS OF A/C | | | C.U. DISCONNECTS. REQ`D WITHIN 6` | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. 659-8096 EXT 8372 |
|