Plan Review Notes
Plan Review Notes For Permit 00060160
Permit Number 00060160
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001) FIRE ALARM SYSTEM TO BE CLASS A
 OR ADDRESSABLE.
 2) FIRE ALARM SYSTEM TO BE AUDIBLE
 THROUGHOUT STORE WHEN ACTIVATED.
 3) SYSTEM TO BE MONITORED BY A LICENSED
 UL LISTED CENTRAL STATION APPROVED
 BY THE FIRE RESCUE DEPARTMENT.