| 2005-04-11 00:00:00 | ************ UNSAT ************* |
| | |
| | *** PLEASE SEE ATTACHED NOTES FROM |
| | 8/27/04 AND PLEASE SEE NEW NOTES DUE TO |
| | MAJOR CHANGES IN PLANS. |
| | |
| | 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 2)NOTE: PLEASE SEE ALL OUTSIDE AND BATH |
| | RECEPTS ARE ALSO TO BE GFI/GFI |
| | PROTECTED. |
| | 210.8 |
| | |
| | 3)NOTE: PLEASE SEE REVISIONS FOR SERVICE |
| | ARE NOW CHANGING FROM THE LAST THREE |
| | REVISIONS SUBMITTED?? |
| | PLEASE SEE PLANS SHOW A "PANEL C" TO BE |
| | FED YET, PLANS AND RISER DO NOT SHOW |
| | THIS PANEL? |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE RISER NOW INDICATES A |
| | 350A SERVICE, PLEASE SEE 250.66, A MIN |
| | OF #2 FOR GROUNDING ELECTRODE CONDUCTOR |
| | IS REQUIRED. |
| | |
| | 5)NOTE: PLEASE SUBMIT COMPLETE PANEL |
| | SCHEDULES INCLUDING ALL OCP AND AWG'S |
| | FOR ALL BRANCH CIRCUITS. |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | PER NEC 220.31/220.31B |
| | |
| | 7)NOTE: PLEASE SEE MISSINF RECEPTS PER |
| | 210.52E/210.8 |
| | |
| | 8)NOTE: PLEASE SEE SERVICE CLEARENCES DO |
| | NOT MEET 110.26, AS PER CONVERSATION |
| | OVER A YEAR AGO, WALL WAS GOING TO BE |
| | MOVED TO MEET MIN 110.26, YET PLANS DO |
| | NOT CORRELATE WITH THIS CHANGE. |
| | |
| | 9)NOTE: PLEASE SEE SD'S SHOWN BOTH |
| | INSIDE MASTER BEDROOM. |
| | PLEASE SEE NFPA-72 8-1.4.1.6.2 |
| | |
| | 10)NOTE: PLEASE CORRELATE ELECTRICAL |
| | LOAD CALCS, PLANS AND MECH PLANS FOR |
| | SIZE OF A/C UNITS/ HEAT STRIPS ETC. |
| | 215.5 |
| | |
| | 11)NOTE: PLEASE SEE SEC'S ARE SHOWN AS |
| | 2/0'S, PLEASE SEE 310.15B6 FOR MIN |
| | SIZING. IF THESE ARE FPL CONDUCTORS, |
| | PLEASE DO NOT INDICATE SIZE, (ONLY IF |
| | FPL OWNED CONDUCTORS). |
| | |
| | 12)NOTE: PLEASE CORRELATE REV DATES ON |
| | TITLE BLOCK WITH PLANS. PLEASE SEE PLANS |
| | INDICATE LAST REVISED DATE OF 4/01 ?? |
| | |
| | 13)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONAL. |
| | IF PLANS COME BACK WITH "ANY" OF THE |
| | SAME COMMENTS FROM PREVIOUS REVIEWS NOT |
| | ADDRESSED, A 4X FEE SHALL BE ACCESSSED |
| | TO THE DESIGN PROFESSIONAL. |
| | |
| | 14)NOTE: PLEASE SEE AS PER PER OUR |
| | RECORDS, NO ELECTRICAL ROUGH INSPECTIONS |
| | WERE EVER MADE UNDER PREVIOUS OR NEW |
| | ELECTRICAL PERMIT. PLEASE SEE 105.6 FBC |
| | FOR REQUIRED INSPECTIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |