| Plan Review Notes For Permit 00060130 |
| Permit Number |
00060130 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-04-15 00:00:00 | DENIED | | | REFERENCE: SBCCI-94 STANDARD PLUMBING | | | | | | CODE | | | SBCCI-97 STANDARD BUILDING | | | CODE | | | | | | 1) SHT S-1 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. CORRECT THE | | | FOLLOWING: | | | A) THE FLOOR DRAINS SHALL HAVE A TRAP | | | PER SECTION 409.4.1.2. | | | B) WASH MACHINE SHALL NOT DRAIN THROUGH | | | THE WET VENT FOR THE BATHROOM FIXTURES. | | | SECTION 611. | | | C) 3" VENT THROUGH THE TIE BEAM IS NOT | | | APPROVED. SECTION 1907.3.6(3). MAXIMUM | | | 2" INSIDE DIAMETER NOMINAL. | | | D) DEAD ENDS NOT APPROVED. SECTION | | | 311.7.3 | | | 2) FLOOR PLAN SHOWS THE FLOOR DRAIN | | | UNDER THE BATH TUB. THE FLOOR DRAIN | | | SHALL BE ACCESSIBLE PER SECTION | | | 409.4.1.2. | | | 3) SEE ATTACHED SHEET FOR AN EXAMPLE OF | | | A SANITARY RISER DIAGRAM THAT REFLECTS | | | THE FLOOR PLAN AND MEETS THE CODE | | | REQUIREMENTS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|