| 2001-03-23 00:00:00 | ****************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT ORIG PLANS |
| | WEREDONE BY ANOTHER ARCH/ENGINEER. |
| | PLANS NEED TO BE RE-DONE BY ORIG ARCH |
| | OF RECORD OR WE NEED A LETTER OF |
| | RELEASEEITHER FROM HOMEOWNER OR FROM |
| | ARCH OF |
| | RECORD. MUST BE A NOTORIZED LETTER. |
| | |
| | 2)NOTE: PLEASE ALSO NOTE THAT ALL PLANS |
| | NEED TO BE SIGNED AND SEALED BY THE |
| | ARCH/ENGINEER OF RECORD. F.A.C. F.S. |
| | 481.221 AND 471.025. THESE PLANS WERE |
| | NOT SIGNED OR SEALED. |
| | |
| | 3)NOTE: PLEASE NOTE THAT NOT ALL NOTES |
| | FROM FRIST REVIEW/PROVISO WERE |
| | ADDRESSEDA NEW SERVICE RISER DIAGRAM IS |
| | NOW BEINGSHOWN. PANEL "B" IS SHOWN AT |
| | 125A AND |
| | ON PLANS IT IS SHOWN AT 60A? |
| | STILL NEED PANEL SCHEDULES TO CLARIFY |
| | ALL REQ`D CIRCUITS. |
| | |
| | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5) NOTE: PLEASE SHOW ALL OUTLETS |
| | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT--ED PER 210-8-A-6. |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 7) NOTE: PLEASE SHOW GROUNDING |
| | ELECTRODEGOING TO BUILDING STEEL AND |
| | COLD WATER |
| | PER 250-50. FROM FIRST REVIEW. |
| | |
| | 8)NOTE: PLEASE NOTE THAT AN EQUIPMENT GR |
| | OUNDING CONDUCTOR IS SHOWN FROM METER |
| | TO FIRST MEANS OF DISC. THIS IS NOT |
| | PERMITTED. |
| | |
| | |
| | PLEASE ADDRESS THE ABOVE COMMENTS. |
| | PLEASE SUBMIT INFORMATION FOR REVIEW. |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 659-8096 EXT 8372 |