| 2001-01-08 00:00:00 | 1)CALCULATIONS FOR COMBUSTION AIR DO NOT |
| | COMPLY W/SGC SEC.402.4.4.4.SUBMIT |
| | REVISED CALCULATIONS.SHOW SIZE OF GRILL |
| | OPENING TOOUTDOORS FROM THE DUCT. |
| | ALLOW 60-75% FOR OPEN AREA FOR METAL AND |
| | 20-25% FOR WOOD. |
| | |
| | 2)SUBMIT DETAIL OF REQUIRED OPENINGS FOR |
| | COMBUSTION AIR.NOTE IF ONE OR TWO OPEN- |
| | INGS ARE USED AND COMPLY W/APPLICABLE |
| | CODE SECS(402.4.4.3 OR 402.4.4.4 OF SGC) |
| | |
| | 3)THERE IS A CONFLICT BETWEEN THE PLBG. |
| | PLANS AND THE MECH.PLANS TO THE LOCATION |
| | OF THE GAS WATER HEATER.CLARIFY THE |
| | LOCATION FOR COMBUSTION AIR REQS. |
| | |
| | 4)DISHWASHER SHALL DISCHARGE TO THE |
| | SANITARY SYSTEM PER CITY WIDE ORDINANCE. |
| | THIS IS NOT CLEARLY SHOWN ON THE PLANS. |
| | |
| | 5)THE DESIGN OF THE GREASY WASTE SYSTEM |
| | AND THE SANITARY FOR RECEIVING THE |
| | INDIRECT WASTES SHALL COMPLY W/SPC |
| | SEC.921 FOR HORIZ.COMBINATION WASTE & |
| | VENT SYSTEM. |
| | |
| | 6)SUBMIT SQ.FEET OF HABITABLE FLOOR |
| | SPACE AND OCCUPANT LOAD TO ENSURE |
| | COMPLIANCE W/SPC TABLE 407.SEE SPC SEC. |
| | 407.1.3 FOR ALLOWED DEDUCTIBLE AREAS. |
| | |
| | 7)CONTROL VALVES ARE REQD.ON THE WATER |
| | BRANCHES INTO THE SPACE PER SPC SEC. |
| | 610.4.2. |
| | |
| | 8)CONDENSATE DRAINS CANNOT DISCHARGE |
| | INTO THE ROOF DRAINS.THEY SHALL CONNECT |
| | TO THE COMMON CONDENSATE SYSTEM.SMC SEC. |
| | 304.8.3. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |