Plan Review Notes
Plan Review Notes For Permit 00060126
Permit Number 00060126
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:001)CALCULATIONS FOR COMBUSTION AIR DO NOT
 COMPLY W/SGC SEC.402.4.4.4.SUBMIT
 REVISED CALCULATIONS.SHOW SIZE OF GRILL
 OPENING TOOUTDOORS FROM THE DUCT.
 ALLOW 60-75% FOR OPEN AREA FOR METAL AND
 20-25% FOR WOOD.
  
 2)SUBMIT DETAIL OF REQUIRED OPENINGS FOR
 COMBUSTION AIR.NOTE IF ONE OR TWO OPEN-
 INGS ARE USED AND COMPLY W/APPLICABLE
 CODE SECS(402.4.4.3 OR 402.4.4.4 OF SGC)
  
 3)THERE IS A CONFLICT BETWEEN THE PLBG.
 PLANS AND THE MECH.PLANS TO THE LOCATION
 OF THE GAS WATER HEATER.CLARIFY THE
 LOCATION FOR COMBUSTION AIR REQS.
  
 4)DISHWASHER SHALL DISCHARGE TO THE
 SANITARY SYSTEM PER CITY WIDE ORDINANCE.
 THIS IS NOT CLEARLY SHOWN ON THE PLANS.
  
 5)THE DESIGN OF THE GREASY WASTE SYSTEM
 AND THE SANITARY FOR RECEIVING THE
 INDIRECT WASTES SHALL COMPLY W/SPC
 SEC.921 FOR HORIZ.COMBINATION WASTE &
 VENT SYSTEM.
  
 6)SUBMIT SQ.FEET OF HABITABLE FLOOR
 SPACE AND OCCUPANT LOAD TO ENSURE
 COMPLIANCE W/SPC TABLE 407.SEE SPC SEC.
 407.1.3 FOR ALLOWED DEDUCTIBLE AREAS.
  
 7)CONTROL VALVES ARE REQD.ON THE WATER
 BRANCHES INTO THE SPACE PER SPC SEC.
 610.4.2.
  
 8)CONDENSATE DRAINS CANNOT DISCHARGE
 INTO THE ROOF DRAINS.THEY SHALL CONNECT
 TO THE COMMON CONDENSATE SYSTEM.SMC SEC.
 304.8.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.