2001-01-08 00:00:001)CALCULATIONS FOR COMBUSTION AIR SHALL
 COMPLY W/SGC SECS.402.4.4.1-402.4.4.4.
  
 2)DISHWASHER SHALL DISCHARGE TO THE
 SANITARY PER CITYWIDE ORDINANCE.
  
 3)THE DESIGN OF THE GREASY WASTE SYSTEM
 SHALL COMPLY W/SPC.SEC.921 FOR HORIZ.
 COMBINATION WASTE AND VENT SYSTEM.
  
 4)SHT.P-4. 4"DRAIN SHOWN DRAINING INTO
 3" LINE.(SEE MEAT PREP AREA.SPC SEC.
 307.5,709.1.
  
 5)SUBMIT SQ. FEET OF HABITABLE FLOOR
 SPACE TO ENSURE COMPLIANCE W/TABLE 407
 FOR MINIMUM PLBG.REQS.
  
 6)MAX.TEMP.OF WATER TO SANITARY SHALL BE
 140 DEGREES.SPC SEC.717.8.
  
 7)WATER SUPPLY CONTROL VALVES ARE REQD.
 ON THE BRANCH LINES PER SPC 610.4.2.