Plan Review Notes For Permit 00060126
Permit Number 00060126
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00PRIMARY STORM DRAINAGE SYSTEM SHALL BE
 DESIGNED PER TABLE 1108.2 OF THE SPC.
 RE:6" ROOF DRAINS AT END OF RUN.
  
 2)PLANS NOTE PIPING TO BE SLOPED AT 3/8"
 PER FT.THIS SLOPE IS NOT LISTED IN TABLE
 1108.2 OF THE SPC.
  
 3)THE LAYOUT OF THE PIPING ON THE PLAN
 SHALL CORRELATE W/THE RISER DIAGRAM.
 COUNTYWIDE AMENDMENT TO SPC SEC.104.2.1.