| Plan Review Notes For Permit 00060126 |
| Permit Number |
00060126 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | **************************************** | | | | | | 1)NOTE: PLEASE SHOW THE SQ.FT CALCULAT- | | | -ION AS PER 220-3-A | | | | | | 2)NOTE: PLEASE SHOW LOAD FOR TRACK LIGHT | | | -ING PER 220-12-B | | | SHOW LOAD FORWINDOW SPACE PER 220-3-A | | | | | | 3)NOTE: PLEASE SHOW WIRE SIZE FOR PANEL | | | (3) ON LINE DIAGRAM. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLANS WOULD HAVE PASSED WITH | | | PROVISOBUT WERE COMING BACK FOR OTHER | | | COMMENTS. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 | | | | | | ALOS PLEASE SEE NOTES TO ART;250-66 OF | | | NEC FOR GROUNDING ELECTRODE CONDUCTOR. | | | 12 1/2 % FOR COMBINED CONDUCTORS. |
|