Plan Review Notes
Plan Review Notes For Permit 00060126
Permit Number 00060126
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 SHT.A-1-WIDTH OF HANDICAP STALLS SHALL
 COMPLY W/FACBC SEC.4.17.3.PRESENT DESIGN
 DOESN'T COMPLY FOR CLEAR FLOOR SPACE
 REQS.
  
 SUBMIT INFORMATION/DETAILS FOR ROOF
 DRAINAGE.COMPLY W/SPC SEC.1108.1,1108.2.
 INCLUDE INFO FOR SECONDARY DRAINAGE PER
 SPC SEC.1109.
  
 WATER FILTRATION SYSTEM SHALL BE NSF
 APPROVED PER SPC SEC.615.1, 615.2.
 SUBMIT MANUF.INFO.
  
 ALL WASTE FROM FLOOR SINKS, FLOOR DRAINS
 HAND SINKS,ETC.IN THE FOOD PREP AND
 SERVING AREA SHALL DISCHARGE THROUGH THE
 GREASE INTERCEPTOR PER SPC SEC.1004.4.
 DISHWASHER SHALL DRAIN TO SANITARY PER
 CITY OF WPB ORDINANCE.
  
 FLOOR SINKS AND FLOOR DRAINS ARE NOT
 PROPERLY VENTED AND EXCEED THE ALLOWABLE
 DISTANCE FROM A VENT PER COUNTYWIDE
 AMENDMENTS TO SPC TABLE 908.1.
  
 CLARIFY SLOPE OF PIPE FOR SANITARY AND
 GREASY WASTE.SHTS.P-4 & P-5 NOTE 1/4"
 AND P-1 NOTES 1/8" INCH.COMPLY W/TABLE
 714.1.
  
 SHT.P-4-SHOWS 4" LINE DISCHARGING INTO
 3" LINE.SEE MEAT PREP AREAS.SPC SEC.
 307.5,709.1.
  
 SHT.P-5-DRY VENTS NOT PERMITTED PER SPC
 906.2.1.(SEE CARTS AREA.)
  
 WATER HEATERS SHALL BE READILY ACCESS-
 IBLE PER SPC SEC.501.7.SUPPLY PERMANENT
 LADDER OR RELOCATE WATER HEATERS TO
 FLOOR.
  
 PLANS SHOW WATER TEMP.AT 180 DEGREES.
 MAX.TEMP.SHALL BE 140 DEGREES PER SPC
 SEC.717.8.MAX.TEMP. OF WATER TO RESTROOM
 SHALL BE 110 DEGREES PER FL.ENERGY CODE
 SEC.412.1.ABCD.2.3.2.
  
 MAIN SHUTOFF VALVE REQD.ON THE WATER
 SUPPLY PER SPC SEC.610.1.
  
 WATER SUPPLY SYSTEM IS LACKING CONTROL
 VALVES.COMPLY W/SPC SEC.610.4.1.
  
 WATER SUPPLY CONTROL VALVES REQD.ON
 BRANCH LINES PER SPC SEC.610.4.2.
  
 SHT.P-6-CLARIFY INFO ON GAS LEGEND.GAS
 PRESSURE AND PRESSURE DROP IS SHOWN AS
 50" AND SPECIFIC GRAVITY IS SHOWN AS 60"
 COMPLY W/SGC SEC.305.4
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR WATER HEATER.COMPLY W/SGC SEC.402.4.
  
 SUBMIT DETAIL OF GREASE INTERCEPTOR.
 CAPACITY SHALL BE APPROVED BTY CITY OF
 WPB UTILITIES.CONTACT R.COMPO AT 561-
 835 7423.
  
 MEZZANINE TOILET ROOMS-DOORS CANNOT
 SWING INTO CLEAR FLOOR SPACE REQD.FOR
 HANDICAP FIXTURES.COMPLY W/FACBC SEC.
 4.2.3.