| 2001-01-08 00:00:00 | 1) EXIT DOOR LOCATIONS NOT CLEARLY |
| | SHOWN ON PLANS. |
| | 2) INTERIOR FINISH SHALL BE CLASS A OR |
| | B. |
| | 3) NO ADDRESS SHOWN ON ELEVATION |
| | DRAWINGS. |
| | 4) PROVIDE COMPLETE PLANS AND PERMITS |
| | FOR THE INSTALLATION OF THE HOOD, DUCT |
| | AND EXTINGUISHING SYSTEMS. SYSTEMS TO |
| | COMPLY WITH NFPA 96 AND 17A. |
| | 5) PROVIDE COMPLETE SHOP DRAWINGS FOR |
| | THE INSTALLATION OF THE FIRE ALARM |
| | SYSTEM. CUT SHEETS ON DEVICES PLANNED |
| | FOR USE ARE NEEDED. FIRE ALARM SYSTEM |
| | IS TO BE AUDIBLE THROUGHOUT THE |
| | BUILDING WHEN ACTIVATED. WHEN ACTIVATED |
| | THE HOOD SYSTEM IS TO ACTIVATE THE |
| | FIRE ALARM SYSTEM. |
| | 6) THE STORAGE OF CARTS ARE NOT TO |
| | INTERFERE WITH ANY EXIT ACCESS OR |
| | EXITING. |
| | 7) GAS INSTALLATION TO COMPLY WITH |
| | NFPA 54. |
| | 8) LOOSE SEATING IS TO PROVIDE A |
| | MINIMUM OF 12 INCHES BETWEEN THE BACKS |
| | OF THE CHAIRS. SEATING SUBJECT TO |
| | APPROVAL. |
| | 9) TRAVEL DISTANCES TO EXITS SHALL NOT |
| | EXCEED 150 FEET. TWO EXITS ARE REQUIRED |
| | FROM BOTH LEVELS. |
| | 10) PORTABLE FIRE EXTINGUISHERS |
| | REQUIRED THROUGHOUT BUILDING. |
| | 11) AISLES TO BE A MINIMUM OF 36 INCHES |
| | IN CLEAR WIDTH. |