2001-01-08 00:00:001) EXIT DOOR LOCATIONS NOT CLEARLY
 SHOWN ON PLANS.
 2) INTERIOR FINISH SHALL BE CLASS A OR
 B.
 3) NO ADDRESS SHOWN ON ELEVATION
 DRAWINGS.
 4) PROVIDE COMPLETE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE HOOD, DUCT
 AND EXTINGUISHING SYSTEMS. SYSTEMS TO
 COMPLY WITH NFPA 96 AND 17A.
 5) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE INSTALLATION OF THE FIRE ALARM
 SYSTEM. CUT SHEETS ON DEVICES PLANNED
 FOR USE ARE NEEDED. FIRE ALARM SYSTEM
 IS TO BE AUDIBLE THROUGHOUT THE
 BUILDING WHEN ACTIVATED. WHEN ACTIVATED
 THE HOOD SYSTEM IS TO ACTIVATE THE
 FIRE ALARM SYSTEM.
 6) THE STORAGE OF CARTS ARE NOT TO
 INTERFERE WITH ANY EXIT ACCESS OR
 EXITING.
 7) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 8) LOOSE SEATING IS TO PROVIDE A
 MINIMUM OF 12 INCHES BETWEEN THE BACKS
 OF THE CHAIRS. SEATING SUBJECT TO
 APPROVAL.
 9) TRAVEL DISTANCES TO EXITS SHALL NOT
 EXCEED 150 FEET. TWO EXITS ARE REQUIRED
 FROM BOTH LEVELS.
 10) PORTABLE FIRE EXTINGUISHERS
 REQUIRED THROUGHOUT BUILDING.
 11) AISLES TO BE A MINIMUM OF 36 INCHES
 IN CLEAR WIDTH.