Plan Review Notes
Plan Review Notes For Permit 00060126
Permit Number 00060126
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT A LIGHTING PLAN.
 PLEASE SHOW LIGHTING FIXTURE LAYOUT AND
 FIXTURE SCHEDULE GIVING FIXTURE LOCATION
 -S.
  
 2)NOTE:PLEASE SHOW AND/OR INDICATE ALL
 CONTINUOUS LOADS IN LOAD CALCULATIONS,
 LOADS FOR LIGHTING ETC. 3 OR MORE HOURS
 NEEDS TO BE SHOWN AT 125%.
 PLEASE SHOW THE ADDED 25% FOR THE LARGE-
 -ST MOTOR LOADS ON EACH PANEL.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372