| Plan Review Notes For Permit 00060126 |
| Permit Number |
00060126 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT A LIGHTING PLAN. | | | PLEASE SHOW LIGHTING FIXTURE LAYOUT AND | | | FIXTURE SCHEDULE GIVING FIXTURE LOCATION | | | -S. | | | | | | 2)NOTE:PLEASE SHOW AND/OR INDICATE ALL | | | CONTINUOUS LOADS IN LOAD CALCULATIONS, | | | LOADS FOR LIGHTING ETC. 3 OR MORE HOURS | | | NEEDS TO BE SHOWN AT 125%. | | | PLEASE SHOW THE ADDED 25% FOR THE LARGE- | | | -ST MOTOR LOADS ON EACH PANEL. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|