| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. DUCT SMOKE DETECTOR REQUIRED FOR FAN | | | SHUT DOWN | | | 2. NOTIFICATION OF FAN SHUT DOWN REQUIRE | | | PER NFPA 4-4.4 | | | 3.OVERFLOW PROTECTION REQUIRED FOR AHU | | | 4.COND. UNIT TO BE ON SOLID CONCRETE PAD | | | MIN. 3' ABOVE FINISHED GRADE |
|