| Plan Review Notes For Permit 00060122 |
| Permit Number |
00060122 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | O************* PROVISO ***************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS WITH ALL | | | BRANCH CIRCUIT #`S SHOWN. 215-5 | | | | | | 2)NOTE: PLEASE DO A RECOUNT ON OUTLETS | | | PER 220-13 | | | | | | 3)NOTE: PLEASE NOTE THAT PANEL SCHEDULE | | | SHOWS MLO, AND RISER DIAGRAM SHOWS MCB? | | | PLEASE CORRELATE. 215-5 | | | | | | 4)NOTE:PLEASE CHECK THE REQ`MENTS OF ART | | | 220-12-B FOR LOAD CALCULATIONS OF TRACK | | | LIGHTING. | | | ALSO PLEASE NOTE 125% FOR CONTINUOUS | | | LOADS (LIGHTING). PLEASE REFIGURE LOAD | | | CALCULATIONS TO REFLECT. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORAMTION | | | FOR REVIEW. PLEASE SUBMIT FOR REVIEW | | | BEFORE ANY ROUGH ELECTRICAL INSPECTION | | | IS CALLED IN. IF THERE ARE ANY QUESTIONS | | | PLEASECALL 659-8096 EXT 8372 |
|