| Plan Review Notes For Permit 00060121 |
| Permit Number |
00060121 |
|
| Review Stop |
P |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SUBMIT ARCHITECTURAL FLOOR PLANS THAT | | | SHOW THE CORRECT LAYOUT OF THE FIXTURES | | | IN THE HANDICAP STALL IN THE MEN'S | | | TOILET ROOM.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.102.4.1. | | | | | | 2)AN ADDITIONAL STALL IN THE WOMEN'S | | | RESTROOM SHALL COMPLY W/FACBC SEC.4.22.4 | | | (STALL SHALL BE 36" WIDE W/GRAB BARS ON | | | BOTH SIDES AND AN OUTWARD SWINGING DOOR) | | | | | | 3)SUBMIT A REVISED SANITARY AND WATER | | | DIAGRAM FOR THE RELOCATED LAV.AND WATER | | | CLOSET. | | | | | | 4)SUBMIT A SANITARY AND WATER RISER FOR | | | THE NEW PLUMBING WORK ON THE FIRST | | | FLOOR.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | 5)VACUUM RELIEF INSTALLATION SHALL | | | COMPLY W/SPC SEC.507.1.2. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|