| Plan Review Notes For Permit 00060121 |
| Permit Number |
00060121 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | 1.FIRE DAMPER LOCATION REQUIRED TO BE | | | INDICATED ON PLAN AT ANY REQUIRED LOCA- | | | TION 1997 SMC 610 | | | | | | | | | 3 PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 4. SPECIFY DUCT MATERIAL TO BE USED | | | FOR REVIEW OF REQUIRED R- VALUE OF | | | INSULATION | | | NOTE: DUCT SMOKE DETECTOR TO BE TIED | | | TO BUILDING FIRE ALARM OR HORN AND STROB | | | FOR NOTIFICATION PER NFPA 90A 4-4.4 |
|