| 2001-01-08 00:00:00 | 1)SINK IN LUNCH ROOM SHALL COMPLY W/ |
| | FACBC SECS.4.24.1-4.24.7 |
| | |
| | 2)SIZE OF ACCESSIBLE STALL IN MEN'S REST |
| | ROOM SHALL COMPLY W/FACBC SEC.4.17.3. |
| | (MIN.SIZE SHALL BE 83" WIDE). |
| | |
| | 3)SUBMIT DETAILS/MOUNTING HEIGHTS FOR |
| | ALL HANDICAP FIXTURES AND APPURTENANCES. |
| | COMPLY W/ALL APPLICABLE SECTIONS OF THE |
| | FACBC. |
| | |
| | 4)TWO DRINKING FOUNTAINS ARE REQD.PER |
| | SPC TABLE 407 OF SPC AND SHALL BE H.C. |
| | ACCESSIBLE PER FACBC 4.1.3(10)(A). |
| | DRINKING FOUNTAINS ARE REQD.ON EACH |
| | FLOOR. |
| | |
| | 5)SANITARY AND WATER RISER DIAGRAMS |
| | SHALL CORRELATE W/THE FLOOR PLAN.COUNTY- |
| | WIDE AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | 6)INDICATE ON THE PLANS THE TYPE OF |
| | FOOD ITEMS TO BE SOLD AT THE CAFE.CLEAR- |
| | LY SHOW THE FOOD PREPARATION AND KITCHEN |
| | AREAS ON THE PLANS. |
| | |
| | 7)PARTITIONS ARE REQD.BETWEEN URINALS. |
| | SPC SEC.404.3. |
| | |
| | |
| | 8)FLOOR DRAINS ARE REQD.IN THE 1ST.FLR. |
| | TOILET ROOMS PER SPC SEC.409.4.1.1. |
| | |
| | 9)FIXTURE BRANCHES AND WATER CLOSETS NOT |
| | PERMITTED ON WET VENTS PER COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.911.1.1.SEE SEC. |
| | 914.1 FOR CIRCUIT AND LOOP VENTING |
| | SYSTEM.SEE 2ND FLR.TOILET ROOMS. |
| | |
| | 10)NOTE NUMBER OF SEATS IN THE CAFE AREA |
| | AND THE HABITABLE FLOOR SPACE FOR THE |
| | TOTAL SALES AREA TO ENSURE COMPLIANCE W/ |
| | SPC TABLE 407 FOR MIN.SANITARY REQS. |
| | |
| | NOTE:THIS IS THE THIRD REVIEW AND THE |
| | MAJORITY OF THE COMMENTS ARE THE SAME |
| | FROM THE FIRST REVIEW AND HAVE NOT BEEN |
| | PROPERLY ADDRESSED OR NOT NOT ADDRESSED |
| | AT ALL. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |