Plan Review Notes
Plan Review Notes For Permit 00060121
Permit Number 00060121
Review Stop M
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00DENIED:
 REQUIRE DAMPER AT RATED WALLS AND SUBMIT
 DETAIL OF DAMPERS 1997 SMC 610.1.2....
 *PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2...
 *PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
 *REQUIRE A DUCT MATERIAL SCHEDULE AS PER
 FLORIDA ENERGY CODE.
 *GRILLE, DIFFUSERS AND REGISTER SCHEDULE
 TO BE SUBMITTED.
 *PROVIDE DETAIL OF FLEX DUCT CONNECTION.
 *FAN SHUT-DOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION BY FIRE ALARM SYSTEM
 OR TIED-IN TO HORN AND STROBE AS PER
 NFPA 90A 4.4.4.2 AND 4.4.4.3....
 * MINIMUM OF 10' CLEARANCE BETWEEN OUT-
 AIR AND EXHAUST AIR.