| Plan Review Notes For Permit 00060121 |
| Permit Number |
00060121 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) EXIT SIGN ABOVE ESCALATOR OPENING | | | ON SECOND FLOOR APPEARS TO DIRECT | | | PERSONS DOWN ESCALATOR. EXIT SIGN IS | | | NEEDED NEAR ESCALATOR BUT IT SHOULD | | | DIRECT PERSONS AWAY FROM ESCALATOR | | | TOWARDS EXIT LOCATIONS. | | | 2) PROVIDE FIRE ALARM SYSTEM DRAWINGS | | | FOR FIRE ALARM EQUIPMENT SHOWN ON PLANS. | | | A SEPARATE PERMIT IS REQUIRED. | | | 3) EXISTING ELEVATOR SHAFT TO BE | | | FIRE SPRINKLER PROTECTED. | | | 4) IF COOKING THAT PRODUCES SMOKE OR | | | GREASE LADEN VAPORS IS DONE, THEN A | | | HOOD, DUCT AND EXTINGUISHING SYSTEM | | | IS REQUIRED. PLANS AND PERMIT REQUIRED. | | | 5) THIS OFFICE STILL HAS NOT RECEIVED | | | FLAME SPREAD INFORMATION ON ROCK | | | CLIMBING WALL. | | | 6) PLEASE INDICATE FLAME SPREAD OF | | | INTERIOR FINISHES USED WITHIN THE | | | SPACE. |
|