| Date |
Text |
| 2001-01-08 00:00:00 | SINK IN LUNCH ROOM SHALL COMPLY W/FACBC |
| | SECS.4.24.1.-4.24.7. |
| | |
| | LAVATORIES ARE REQD.WITHIN THE H.C. |
| | ACCESSIBLE STALLS PER FACBC SEC.4.17.3. |
| | (SEE EXCEPTION:NEW CONSTRUCTION.)SIZE OF |
| | HANDICAP STALLS SHALL COMPLY W/4.17.3. |
| | |
| | SUBMIT DETAILS/MOUNTING HEIGHTS FOR ALL |
| | HANDICAP FIXTURES AND APPURTENANCES. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| | |
| | TWO DRINKING FOUNTAINS ARE REQD.PER |
| | TABLE 407 OF SPC.AND SHALL BE H.C.ACCES- |
| | IBLE PER FACBC SEC.4.1.3(10)(A). |
| | PROVISIONS SHALL BE MADE FOR PEOPLE WHO |
| | HAVE TROUBLE BENDING OR STOOPING. |
| | |
| | WATER HEATER SHALL BE EQUIPPED W/DRAIN |
| | PAN AND RELIEF DRAIN AND PAN DRAIN SHALL |
| | DISCHARGE TO EXTERIOR PER COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.507.6. |
| | |
| | SHT.P3.01-PLUMBING GENERAL NOTES #5- |
| | DELETE REFERENCE TO MASS.ACCESS BOARD. |
| | ACCESSIBILITY SHALL BE DESIGNED TO |
| | STANDARDS PER FLA.DEPT.OF COMMUNITY |
| | AFFAIRS AND FLA.STATUTE. |
| | |
| | A GATE VALVE IS REQD.ON THE INLET TO THE |
| | WATER HEATER PER SPC SEC.506.1. |
| | |
| | OVER 2 FIXTURES ARE SUPPLIED BY 1/2"C.W. |
| | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.607.7.(SEE 2ND. FLR.) |
| | |
| | FLAT DRY VENTS NOT PERMITTED PER SPC SEC |
| | 906.2.1. |
| | |
| | SANITARY AND WATER RISER DIAGRAMS SHALL |
| | CORRELATE W/THE FLOOR PLAN.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | INDICATE ON PLANS THE TYPE OF ITEMS TO |
| | BE SOLD AT THE CAFE.APPROVAL FROM THE |
| | DEPT. OF BUSINESS REGULATION AND THE |
| | INSTALLATION OF A GREASE TRAP MAY BE |
| | REQD.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 101.4.7,SPC SEC.1004.4. |
| | |
| | CLEANOUTS SHALL BE INSTALLED PER SPC |
| | 710.2. |
| | |
| | FLOOR DRAINS SHALL HAVE TRAP PRIMERS |
| | PER 409.4.1.1. |
| | |
| | ALL SHEETS SHALL BEAR THE DATE,SIGNATURE |
| | AND RAISED SEAL OF THE DESIGN |
| | PROFESSION OF RECORD PER F.S.481.221,& |
| | FLA.RULE 61G15-23.002. |
| | |
| | SHT.P3.03-DESIGN OF SANITARY SYSTEM |
| | SHALL COMPLY W/SPC SEC.914.1-914.2.FOR |
| | A CIRCUIT AND LOOP SYSTYEM. |
| | |
| | VENTING OF WATER CLOSETS IN 2ND.FLR. |
| | TOILET ROOM SHALL COMPLY W/COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.911.1.3. |