Plan Review Notes
Plan Review Notes For Permit 00060121
Permit Number 00060121
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*****************DENIED*****************
 1. RAISED SEAL REQUIRED ON PLANS.
 2. PROVIDE OUTSIDE AIR PER ASHRAE 62-89.
 3. AIR BALANCE SCHEDULE PER 1997 SMC
 501.2
 4. ADDITIONAL MECHANICAL PERMIT REQUIRED
 FOR FIRE SUPPRESSION AND HOOD IF
 THESE ARE TO BE INSTALLED IN BUILDING