| Plan Review Notes For Permit 00060121 |
| Permit Number |
00060121 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH SHALL BE CLASS A OR | | | B. | | | 2) NO HYDRAULIC CALCULATIONS PROVIDED | | | FOR FIRE SPRINKLER DRAWINGS. A SEPARATE | | | PERMIT IS REQUIRED FOR INSTALLTION OF | | | THIS SYSTEM. | | | 3) PROVIDE DETAILS ON CONSTRUCTION OF | | | ROCK CLIMBING WALL. | | | 4) WHAT IS THE ELECTRIC GRILL FOR. ANY | | | COOKING THAT PRODUCES SMOKE OR GREASE | | | LADEN VAPORS IS TO BE PROTECTED BY A | | | HOOD, DUCT AND EXTINGUISHING SYSTEM. A | | | SEPARATE PERMIT IS REQUIRED. | | | 5) EXITS FROM THE SECOND FLOOR NOT | | | PROPER. EXITS ARE TO BE SEPARATED FROM | | | ONE ANOTHER BY AT LEAST 1/2 OF THE | | | MAXIMUM OVERALL DIAGONAL DIMENSION OF | | | THE SPACE. | | | 6) PROVIDE COMPLETE SHOP DRAWINGS FOR | | | THE INSTALLATION OF THE FIRE ALARM | | | SYSTEM EQUIPMENT. CUT SHEETS NEEDED ON | | | ALL DEVICES PLANNED FOR USE. | | | 7) PORTABLE FIRE EXTINGUISHERS REQUIRED | | | THROUGHOUT PREMISES. |
|