| 2001-01-08 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE COMPLETE AND SHOW LOAD |
| | CALCULATIONS ON EACH PANEL. |
| | ALL CONTIUOUS LOADS (LIGHTING ETC) |
| | ARE TO SHOWN IN LOAD CALCS AT 125% |
| | |
| | 2)NOTE: PLEASE SUBMIT AND SHOW THE AIC |
| | RATINGS FOR EACH PANEL/MAIN DISCONNECT. |
| | MAINS/PANELS ARE TO BE RATED FOR THE |
| | AVAILABLE FAULT CURRENT.110-9/215-5 |
| | PLEASE PLACE RATING FOR EACH. |
| | |
| | 3)NOTE: YOU ARE SHOWING ON YOUR NOTES |
| | THAT SIMULATORS AND OTHER EQUIPMENT |
| | LOADS ARE ESTIMATED.? THIS WILL NOT |
| | BE ACCEPTED. PLEASE FIND OUT LOADS AND |
| | SUBMIT FOR LOAD CALCULATIONS. 215-5 |
| | |
| | 4)NOTE:PLEASE GIVE BREAKDOWN ON TRACK |
| | LIGHTING LOAD CALCUALTIONS 220-12-B |
| | |
| | 5)NOTE: PLEASE SEE 450-21-B PLEASE GIVE |
| | MORE DETAIL ON ROOM AND /OR CLASS OF |
| | TRANSFORMER? |
| | |
| | 6)NOTE: PLEASE SEE THE REQ`MENTS FOR |
| | GROUNDING ELECTRODE SYSTEM 250-50. |
| | COLD WATER BOND, AND BONDING GROUNDING |
| | ELECTRODES TOGETHER PER NEC. 250 |
| | |
| | 7)NOTE: PANEL LOAD ARE TO BE VERIFIED |
| | UPON COMPLETION OD LOAD CALCULATIONS. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 561-659-8096 EXT 8372 |