Notes
Date Text
2001-01-08 00:00:00SUBMIT CORRECT OCCUPANT LOAD FOR
 COMPLIANCE W/TABLE 407 OF SPC.SEE SPC
 SEC.407.1.3.FOR ALLOWED DEDUCTIBLE FLOOR
 SPACE.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 SHOW INSIDE CLEAR WIDTH OF TOILET ROOMS
 ON PLANS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 FITTING ROOM SHALL COMPLY W/FACBC SEC.
 4.1.3(21),4.35.THE BENCH SHALL BE FIXED
 ALONG THE LONGER DIMENSION WALL.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER
 OR RELOCATE EWH TO FLOOR.