2001-01-08 00:00:001)INDIRECT WASTES SHALL DISCHARGE INTO A
 FLOOR SINK PER SPC SEC.804.1
  
 2)SYSTEM OF FLOOR DRAINS AND FLOOR SINKS
 SHALL BE INSTALLED ON A HORIZONTAL
 COMBINATION WASTE AND VENT SYSTEM PER
 SPC SEC.921.4.AS DESIGNED FIXTURES ARE
 NOT PROPERLY VENTED.
  
 3)DISHWASHER SHALL DISCHARGE TO THE
 SANITARY SYSTEM PER CITY ORDINANCE.
  
 4)SUBMIT WATER RISER DIAGRAM FOR ALL NEW
 WORK.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 5)SIZE VENT FOR NEW HAND SINK.COMPLY W/
 SPC TABLE 920.2.
  
 6)SUBMIT MANUF.DATA ON PROVENT.SPC 303.1
 303.5.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.