| Plan Review Notes For Permit 00060037 |
| Permit Number |
00060037 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)INDIRECT WASTES SHALL DISCHARGE INTO A | | | FLOOR SINK PER SPC SEC.804.1 | | | | | | 2)SYSTEM OF FLOOR DRAINS AND FLOOR SINKS | | | SHALL BE INSTALLED ON A HORIZONTAL | | | COMBINATION WASTE AND VENT SYSTEM PER | | | SPC SEC.921.4.AS DESIGNED FIXTURES ARE | | | NOT PROPERLY VENTED. | | | | | | 3)DISHWASHER SHALL DISCHARGE TO THE | | | SANITARY SYSTEM PER CITY ORDINANCE. | | | | | | 4)SUBMIT WATER RISER DIAGRAM FOR ALL NEW | | | WORK.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | 5)SIZE VENT FOR NEW HAND SINK.COMPLY W/ | | | SPC TABLE 920.2. | | | | | | 6)SUBMIT MANUF.DATA ON PROVENT.SPC 303.1 | | | 303.5. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|