Plan Review Notes
Plan Review Notes For Permit 00060037
Permit Number 00060037
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***********DENIED**********************
  
 1. 1997 SMC 509.9.2 REQUIRES THE GREASE
 EXHAUST DUCT TO BE ENCLOSED BY AN ENCL-
 OSURE EXCLUSIVELY FOR THE GREASE EXHAUST
 DUCT AND SHALL BE USED FOR NO OTHER PUR-
 POSE. K-5 SHOWS MAKE UP AIR DUCT IN WITH
 GREASE EXHAUST DUCT.
 2. 1997 SMC 304.2.5 (MODEL COUNTYWIDE
 AMENDMENTS AS ADOPTED BY THE CITY OF
 WEST PALM BEACH) REQUIRES MIN. 18" OF
 CLEARANCE UNDER MECHANICAL EQUIPMENT ON
 ROOF. MEASURE FROM BOTTOM OF SUPPORT
 STRUCTURE TO FINISH SURFACE OF ROOF.
 3. EXHAUST FAN TERMINATION ABOVE ROOF IS
 FROM THE EXHAUST OUTLET OF THE FAN
 4. STATE OF FLORIDA ENERGY EFFICIENCY
 CODE PROHIBITS CONDENSING UNITS FROM
 BEING PLACED IN THE COOL AIR STREAM OF
 ANOTHER UNIT. WHERE ARE WALK- IN COOLER
 FREEZER CONDENSING UNITS?
 5. PROVIDE ROOF TOP PLAN SHOWING PLACE-
 MENT OF EQUIPMENT FOR REVIEW PURPOSES
 6. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 7. SEPARATE PERMIT REQUIRED FOR KITCHEN
 HOOD. PROVIDE PLANS FOR HOODS,DUCT, FANS
 ETC. AT TIME OF MECHANICAL PERMIT APPL
 FOR HOODS
 8. SEPARATE PERMITS REQUIRED FOR WALK IN
 COOLERS/ FREEZERS. PROVIDE PLANS AT TIME
 OF PERMIT APPLICATION
 9. PROVIDE DETAILS ONSOURCE OF TEMPER-
 ED AIR TO BE SUPPLIED TO HOOD FROM MC
 AS SHOWN ON PLAN (M-4)