Plan Review Notes
Plan Review Notes For Permit 00060037
Permit Number 00060037
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AND PROVIDE PANEL
 SCHEDULES FOR EXISTING PANELS WITH ALL
 BRANCH CIRCUITS SHOWN.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 INCLUDING ALL NEW EQUIPMENT LOADS AND
 ALL EXISTING LOADS.215-5
 LOADS FOR CONTINUOUS LOADS TO BE FIGURED
 AT 125%. PLEASE SHOW.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372