| Date |
Text |
| 2001-01-08 00:00:00 | PLANS SHALL BE ROUTED TO DEPT.OF |
| | BUSINESS REGULATION FOR REVIEW AND |
| | APPROVAL.SUBMIT APPROVAL DOCUMENTATION |
| | FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.101.4.7. |
| | |
| | ALL FLOOR SINKS ,HAND SINKS,FLOOR DRAINS |
| | ETC.IN THE FOOD PREP/KITCHEN/BAR AREAS |
| | SHALL DISCHARGE THRU THE GREASY WASTE |
| | SYSTEM EXCEPT THE DISHWASHER AND THE |
| | FOOD WASTE GRINDER.SPC 1004.4. |
| | |
| | THE GAS MANIFOLD AT THE METER SHALL |
| | COMPLY W/NFPA 54 FOR DISTANCE FROM |
| | SOURCE OF IGNITION.THIS WILL BE SUBJECT |
| | TO FIELD INSPECTION AND IF FOUND TO BE |
| | IN VIOLATION SHALL BE RELOCATED.THIS |
| | ISSUE WAS ADDRESSED ON THE SHELL |
| | BUILDING AND REQUIRES COMPLIANCE. |
| | |
| | A SIGNED,SEALED AND DATED SANITARY AND |
| | WATER ISOMETRIC DRAWING SHALL BE |
| | SUBMITTED FOR REVIEW PRIOR TO PLUMBING |
| | INSPECTION.THE DRAWINGS SHALL CORRELATE |
| | WITH THE FLOOR PLANS AND COMPLY W/SPC |
| | FOR DESIGN IN ALL RESPECTS.THERE ARE |
| | TOO MANY VIOLATIONS OF THE CODE TO LIST. |
| | SEE PREVIOUS COMMENTS.COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC.104.2.1. |
| | |
| | WATER HEATER SHALL BE READILY ACCESSIBLE |
| | PER SPC 507.1.SUPPLY FIXED LADDER OR |
| | RELOCATE HEATER TO FLOOR.HEATERS LOCATED |
| | ABOVE THE FIRST FLOOR CEILING SHALL |
| | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.507.8.1.LADDER IS NOT SHOWN ON ARCH. |
| | DRAWINGS. |
| | |
| | SUBMIT COPY OF APPROVAL FROM WPB |
| | UTILITIES DEPT.FOR GREASE TRAP.CONTACT |
| | R.COMPO AT 561-835-7423. |
| | |
| | AN ADDITIONAL WATER CLOSET IS REQD.IN |
| | MALE AND FEMALE RESTROOMS PER TABLE 407 |
| | OF SPC AND SEC.407.2.2. |
| | |
| | SIZE DROPS TO GAS EQUIPMENT TO ENSURE |
| | COMPLIANCE W/SGC TABLE 305.4(A).THE |
| | TABLE REFERENCED ON THE PLANS DOES NOT |
| | EXIST IN THE SGC. |
| | |
| | IF YOU HAVE ANY QUESTIONS I CAN BE |
| | REACHED AT 561-659-8096,EXT.8377. |
| | T.LARGE PLUMBING PLANS EXAMINER. |