Notes
Date Text
2001-01-08 00:00:00PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL.SUBMIT APPROVAL DOCUMENTATION
 FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 ALL FLOOR SINKS ,HAND SINKS,FLOOR DRAINS
 ETC.IN THE FOOD PREP/KITCHEN/BAR AREAS
 SHALL DISCHARGE THRU THE GREASY WASTE
 SYSTEM EXCEPT THE DISHWASHER AND THE
 FOOD WASTE GRINDER.SPC 1004.4.
  
 THE GAS MANIFOLD AT THE METER SHALL
 COMPLY W/NFPA 54 FOR DISTANCE FROM
 SOURCE OF IGNITION.THIS WILL BE SUBJECT
 TO FIELD INSPECTION AND IF FOUND TO BE
 IN VIOLATION SHALL BE RELOCATED.THIS
 ISSUE WAS ADDRESSED ON THE SHELL
 BUILDING AND REQUIRES COMPLIANCE.
  
 A SIGNED,SEALED AND DATED SANITARY AND
 WATER ISOMETRIC DRAWING SHALL BE
 SUBMITTED FOR REVIEW PRIOR TO PLUMBING
 INSPECTION.THE DRAWINGS SHALL CORRELATE
 WITH THE FLOOR PLANS AND COMPLY W/SPC
 FOR DESIGN IN ALL RESPECTS.THERE ARE
 TOO MANY VIOLATIONS OF THE CODE TO LIST.
 SEE PREVIOUS COMMENTS.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC 507.1.SUPPLY FIXED LADDER OR
 RELOCATE HEATER TO FLOOR.HEATERS LOCATED
 ABOVE THE FIRST FLOOR CEILING SHALL
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.507.8.1.LADDER IS NOT SHOWN ON ARCH.
 DRAWINGS.
  
 SUBMIT COPY OF APPROVAL FROM WPB
 UTILITIES DEPT.FOR GREASE TRAP.CONTACT
 R.COMPO AT 561-835-7423.
  
 AN ADDITIONAL WATER CLOSET IS REQD.IN
 MALE AND FEMALE RESTROOMS PER TABLE 407
 OF SPC AND SEC.407.2.2.
  
 SIZE DROPS TO GAS EQUIPMENT TO ENSURE
 COMPLIANCE W/SGC TABLE 305.4(A).THE
 TABLE REFERENCED ON THE PLANS DOES NOT
 EXIST IN THE SGC.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.
 T.LARGE PLUMBING PLANS EXAMINER.