| Plan Review Notes For Permit 00051840 |
| Permit Number |
00051840 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) ALL FABRIC AWNINGS ARE TO BE FLAME | | | RETARDANT. | | | 2) HYDRAULIC CALCULATION SUMMARY IS NOT | | | CORRECT. WHERE DID THESE FIGURES COME | | | FROM. | | | 3) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 4) PROVIDE FIRE ALARM SYSTEM DRAWINGS | | | FOR FIRE ALARM SYSTEM EQUIPMENT SHOWN | | | ON PLANS. A SEPARATE PLAN AND PERMIT | | | REQUIRED. | | | 5) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 6) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 7) PROVIDE COMPLETE HOOD, DUCT, AND | | | EXTINGUISHING PLANS. A SEPARATE PERMIT | | | IS REQUIRED. |
|