Plan Review Notes
Plan Review Notes For Permit 00051840
Permit Number 00051840
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHT.A0.1-CLARIFY OCCUPANCY GROUP.PLANS
 NOTE A-3.THERE IS NO SUCH CLASSIFICATION
 IN THE STANDARD BUILDING CODE.
  
 PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
  
 URINAL SHALL BE INSTALLED AT HANDICAP
 HEIGHT PER FACBC SEC.4.18.2.
  
 SHT.A7.1-INDICATE ROOM FINISHES.TOILET
 ROOMS AND RESTROOMS SHALL COMPLY W/SBC
 SEC.1204.2.
  
 ALL FLOOR SINKS,HAND SINKS,FLOOR DRAINS,
 ETC.IN THE FOOD PREP/KITCHEN AREA SHALL
 DISCHARGE THROUGH THE GREASE INTERCEPTOR
 PER SPC SEC.1004.4.
  
 PUMPED DISCHARGE SYSTEM(EJECTORS)SHALL
 COMPLY W/SPC SEC.717.2-717.11.SUBMIT
 INFO ON BASIN,PUMPS,ETC.COMPLY W/SPC
 FOR CONNECTION TO SANITARY SYSTEM.
  
 SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT.
 ALL EQUIPMENT SHALL BE LISTED PER SGC
 SEC.402.1 AND NFPA 54.
  
 SHOW ALL CUT DIMENSIONS OF GAS PIPING,
 TYPE OF GAS,LOCATION OF GAS METER,
 DELIVERY PRESSURE,AND SUBMIT COPY OF OR
 REFERENCE APPLICABLE SIZING TABLE USED
 IN SYSTEM DESIGN.SGC SEC 305.4.
  
 SUBMIT DETAIL OF GAS MANIFOLD.COMPLIANCE
 W/NFPA 54 SHALL BE REQUIRED FOR DISTANCE
 TO SOURCE OF IGNITION IF APPLICABLE.
  
 THE LAYOUT OF THE 2ND FLR.TOILET ROOMS
 IS NOT CONSTANT THROUGHOUT THE DRAWINGS.
 CLARIFY CORRECT LAYOUT.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 THE SCHEMATIC FOR THE GREASY WASTE DOES
 NOT CORRELATE W/THE PLAN DRAWING.PLEASE
 REVISE.SEE SHT.P5.
  
 FLOOR SINKS AND FLOOR DRAINS ARE NOT
 PROPERLY VENTED.SPC SEC.901.2.
  
 VENT CONNECTIONS TO EXIST.ARE SHOWN AS
 3"ON P2 AND AS 2"0N P-5.CLARIFY.
  
 SCHEMATIC "A" DOESN'T CORRELATE W/FLOOR
 PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 WASTE AND VENT RISER "A"-WATER CLOSETS
 AND FIXTURE BRANCHES NOT PERMITTED ON
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.CIRCUIT AND LOOP SYSTEM
 SHALL COMPLY W/SPC SEC.914.1 IF THAT IS
 THE INTENT.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1,610.4.2.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.507.1.SUPPLY FIXED LADDER OR
 RELOCATE TO FLOOR.HEATERS LOCATED ABOVE
 THE 1ST FLOOR CEILING SHALL COMPLY W/
 COUNTYWIDE AMENDMENTS TO SPC SEC.507.8.1
  
 WATER FILTRATION SYSTEM SHALL BE NSF
 APPROVED PER SPC SEC.615.1.SUBMIT INFO.
  
 FLOOR DRAINS ARE REQUIRED IN THE FIRST
 FLOOR TOILET ROOMS PER SPC SEC.409.4.1.1
 AND SHALL BE EQUIPPED W/TRAP PRIMERS.
  
 THE SIZE OF THE HANDICAP TOILET STALLS
 SHALL COMPLY W/FACBC 4.17.3 AND FIG.30.
  
 A UNION OR FLANGED CONNECTION IS REQD.
 DOWNSTREAM OF F.A.VALVE PER NFPA 54 SEC.
 5.5.3.
  
 APPROVAL FOR GREASE TRAP CAPACITY IS
 REQD.FROM CITY OF WPB UTILITIES.CONTACT
 R.COMPO AT 561-835-7423.
  
 IF THERE ARE ANY QUESTIONS YOU MAY
 CONTACT ME AT (561)659-8096,EXT.8377.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved