| Date |
Text |
| 2001-01-08 00:00:00 | SHT.A0.1-CLARIFY OCCUPANCY GROUP.PLANS |
| | NOTE A-3.THERE IS NO SUCH CLASSIFICATION |
| | IN THE STANDARD BUILDING CODE. |
| | |
| | PLANS SHALL BE ROUTED TO DEPT.OF |
| | BUSINESS REGULATION FOR REVIEW.COUNTY- |
| | WIDE AMENDMENTS TO SPC SEC.101.4.7. |
| | |
| | URINAL SHALL BE INSTALLED AT HANDICAP |
| | HEIGHT PER FACBC SEC.4.18.2. |
| | |
| | SHT.A7.1-INDICATE ROOM FINISHES.TOILET |
| | ROOMS AND RESTROOMS SHALL COMPLY W/SBC |
| | SEC.1204.2. |
| | |
| | ALL FLOOR SINKS,HAND SINKS,FLOOR DRAINS, |
| | ETC.IN THE FOOD PREP/KITCHEN AREA SHALL |
| | DISCHARGE THROUGH THE GREASE INTERCEPTOR |
| | PER SPC SEC.1004.4. |
| | |
| | PUMPED DISCHARGE SYSTEM(EJECTORS)SHALL |
| | COMPLY W/SPC SEC.717.2-717.11.SUBMIT |
| | INFO ON BASIN,PUMPS,ETC.COMPLY W/SPC |
| | FOR CONNECTION TO SANITARY SYSTEM. |
| | |
| | SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT. |
| | ALL EQUIPMENT SHALL BE LISTED PER SGC |
| | SEC.402.1 AND NFPA 54. |
| | |
| | SHOW ALL CUT DIMENSIONS OF GAS PIPING, |
| | TYPE OF GAS,LOCATION OF GAS METER, |
| | DELIVERY PRESSURE,AND SUBMIT COPY OF OR |
| | REFERENCE APPLICABLE SIZING TABLE USED |
| | IN SYSTEM DESIGN.SGC SEC 305.4. |
| | |
| | SUBMIT DETAIL OF GAS MANIFOLD.COMPLIANCE |
| | W/NFPA 54 SHALL BE REQUIRED FOR DISTANCE |
| | TO SOURCE OF IGNITION IF APPLICABLE. |
| | |
| | THE LAYOUT OF THE 2ND FLR.TOILET ROOMS |
| | IS NOT CONSTANT THROUGHOUT THE DRAWINGS. |
| | CLARIFY CORRECT LAYOUT.COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC.104.2.1. |
| | |
| | THE SCHEMATIC FOR THE GREASY WASTE DOES |
| | NOT CORRELATE W/THE PLAN DRAWING.PLEASE |
| | REVISE.SEE SHT.P5. |
| | |
| | FLOOR SINKS AND FLOOR DRAINS ARE NOT |
| | PROPERLY VENTED.SPC SEC.901.2. |
| | |
| | VENT CONNECTIONS TO EXIST.ARE SHOWN AS |
| | 3"ON P2 AND AS 2"0N P-5.CLARIFY. |
| | |
| | SCHEMATIC "A" DOESN'T CORRELATE W/FLOOR |
| | PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 104.2.1. |
| | |
| | WASTE AND VENT RISER "A"-WATER CLOSETS |
| | AND FIXTURE BRANCHES NOT PERMITTED ON |
| | WET VENTS PER COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.911.1.1.CIRCUIT AND LOOP SYSTEM |
| | SHALL COMPLY W/SPC SEC.914.1 IF THAT IS |
| | THE INTENT. |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/SPC |
| | SEC.610.4.1,610.4.2. |
| | |
| | WATER HEATER SHALL BE READILY ACCESSIBLE |
| | PER SPC SEC.507.1.SUPPLY FIXED LADDER OR |
| | RELOCATE TO FLOOR.HEATERS LOCATED ABOVE |
| | THE 1ST FLOOR CEILING SHALL COMPLY W/ |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.507.8.1 |
| | |
| | WATER FILTRATION SYSTEM SHALL BE NSF |
| | APPROVED PER SPC SEC.615.1.SUBMIT INFO. |
| | |
| | FLOOR DRAINS ARE REQUIRED IN THE FIRST |
| | FLOOR TOILET ROOMS PER SPC SEC.409.4.1.1 |
| | AND SHALL BE EQUIPPED W/TRAP PRIMERS. |
| | |
| | THE SIZE OF THE HANDICAP TOILET STALLS |
| | SHALL COMPLY W/FACBC 4.17.3 AND FIG.30. |
| | |
| | A UNION OR FLANGED CONNECTION IS REQD. |
| | DOWNSTREAM OF F.A.VALVE PER NFPA 54 SEC. |
| | 5.5.3. |
| | |
| | APPROVAL FOR GREASE TRAP CAPACITY IS |
| | REQD.FROM CITY OF WPB UTILITIES.CONTACT |
| | R.COMPO AT 561-835-7423. |
| | |
| | IF THERE ARE ANY QUESTIONS YOU MAY |
| | CONTACT ME AT (561)659-8096,EXT.8377. |