| 2001-01-08 00:00:00 | **************DENIED******************* | | | | | | 1) OUTSIDE AIR REQUIRED PER ASHRAE 62-89 | | | 2) PROVIDE AIR BALANCE SCHEDULE PER 1997 | | | 501.2 | | | 3) SPECIFY MATERIALS FOR AIR DUCTS | | | 4) DUCT SMOKE DETECTORS TO BE TIED TO | | | BUILDING FIRE ALARM SYSTEM PER NFPA 90A | | | 5) EQUIPMENT ON ROOF TO PROVIDE MIN. | | | CLEARANCE OF 18" BETWEEN SURFACE OF ROOF | | | AND BOTTOM OF SUPPORT STRUCTURE OF STAND | | | FOR ROOF ACCESS UNDER EQUIPMENT PER | | | LOCAL ORDINANCE | | | 6) SEPERATE PERMITS REQUIRED FOR HOODS, | | | WALKIN COOLERS/FREEZERS, AND SUPPRESSION | | | SYSTEMS. SUBMIT PLANS AT TIME OF PERMIT | | | APPLICATION FOR THESE SYSTEMS |
|