| Plan Review Notes For Permit 00051840 |
| Permit Number |
00051840 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS OF ALL | | | MAIN DISCONNECTS/PANELS. MAINS/PANELS | | | MUST BE RATED FOR THE AVAILABLE FAULT | | | CURRENT. 110-9/215-5 | | | | | | 2)NOTE: PLEASE NOTE YOU ARE SHOWING A | | | 150KVA TRANSFORMER WITH 150C TEMP RISE. | | | PLEASE SEE ART;450-21-B EXCEPT. #1 | | | MUST HAVE TEMP RISE 155 C. | | | PLEASE ADJUST OR TRANSFORMER MUST BE | | | INSTALLED IN TRANSFORMER VAULT/ROOM | | | UNDER NEC. REQ`MENTS. | | | | | | 3)NOTE: YOU SHOW PANEL "HVPP" ON SHEET | | | E-6. PLEASE INCLUDE THIS ON THE ONE-LINE | | | RISER DIAGRAM. 215-5 | | | | | | 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS! | | | LOAD CALCULATIONS TO MEET REQ`MENTS OF | | | THE NEC. ALSO PLEASE INCLUDE ALL LOADS | | | THAT MAY BE CONTINUOUS. (LIGHTING ETC) | | | PLEASE SUBMIT THE BREAK DOWN ON EACH | | | PANEL AND TOTAL LOAD ON MAIN LVMDP. | | | PLEASE SUBMIT THE LOAD CALCULATION FOR | | | PANEL "HVPP". SHOW BREAK DOWN ON LOADS | | | AND SHOW LOADS OF EQUIPMENT. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW.IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 |
|