Plan Review Notes
Plan Review Notes For Permit 00051840
Permit Number 00051840
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS OF ALL
 MAIN DISCONNECTS/PANELS. MAINS/PANELS
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT. 110-9/215-5
  
 2)NOTE: PLEASE NOTE YOU ARE SHOWING A
 150KVA TRANSFORMER WITH 150C TEMP RISE.
 PLEASE SEE ART;450-21-B EXCEPT. #1
 MUST HAVE TEMP RISE 155 C.
 PLEASE ADJUST OR TRANSFORMER MUST BE
 INSTALLED IN TRANSFORMER VAULT/ROOM
 UNDER NEC. REQ`MENTS.
  
 3)NOTE: YOU SHOW PANEL "HVPP" ON SHEET
 E-6. PLEASE INCLUDE THIS ON THE ONE-LINE
 RISER DIAGRAM. 215-5
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS!
 LOAD CALCULATIONS TO MEET REQ`MENTS OF
 THE NEC. ALSO PLEASE INCLUDE ALL LOADS
 THAT MAY BE CONTINUOUS. (LIGHTING ETC)
 PLEASE SUBMIT THE BREAK DOWN ON EACH
 PANEL AND TOTAL LOAD ON MAIN LVMDP.
 PLEASE SUBMIT THE LOAD CALCULATION FOR
 PANEL "HVPP". SHOW BREAK DOWN ON LOADS
 AND SHOW LOADS OF EQUIPMENT.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372