| Plan Review Notes For Permit 00051838 |
| Permit Number |
00051838 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | BATHROOM SHALL BE HANDICAP ACCESSIBLE | | | PER FACBC SEC.4.1.3.(11),4.1.6.(1)(B). | | | | | | SUBMIT DETAILS/MOUNTING HEIGHT OF ALL | | | HANDICAP FIXTURES AND APPURTENANCES. | | | COMPLY W/FACBC OCT.1997 EDITION. | | | | | | DOOR TO TOILET ROOM SHALL COMPLY W/SEC. | | | 4.13 OF FACBC. | | | | | | SHOW TURNING SPACE FOR WHEELCHAIR PER | | | FACBC SEC.4.2.3. | | | | | | SUBMIT WATER RISER FOR REVIEW PER COUNTY | | | WIDE AMENDMENTS TO SPC SEC.104.2.1. | | | | | | SHOW FIXTURE CLEARANCE OF WATER CLOSET | | | FROM WALL TO CENTER OF W.C.COMPLY W/ | | | FACBC FIG.28. | | | | | | FLOOR AND WALLS SHALL BE NONABSORBENT TO | | | A HEIGHT OF 4'PER SBC SEC.1204.2. | | | | | | A FLOOR DRAIN W/TRAP PRIMER IS REQD.IN | | | THE TOILET ROOM PER SPC SEC.409.4.1.1. |
|