Plan Review Notes
Plan Review Notes For Permit 00051663
Permit Number 00051663
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOM. NFPA-72 2-2.1.1.1
  
 2)NOTE: MISSING OUTLET SPACING TO MEET
 CODE IN BEDROOM. 210-52
  
 3)NOTE: MISSING EGRESS LIGHTING PER
 CODE 210-70
  
 4)NOTE: PLEASE LABEL ALL OULTETS FOR
 PORCH AS GFI/GFI PROTECTED. 210-8
  
 5)NOTE: PLEASE PROVIDE REVISED PANEL
 SCHEDULE SHOWING THE REQ`D DEDICATED
 CIRCUIT FOR BATH(S). MUST BE #12 AND 20A
 AS PER 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372