| Plan Review Notes For Permit 00051663 |
| Permit Number |
00051663 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOM. NFPA-72 2-2.1.1.1 | | | | | | 2)NOTE: MISSING OUTLET SPACING TO MEET | | | CODE IN BEDROOM. 210-52 | | | | | | 3)NOTE: MISSING EGRESS LIGHTING PER | | | CODE 210-70 | | | | | | 4)NOTE: PLEASE LABEL ALL OULTETS FOR | | | PORCH AS GFI/GFI PROTECTED. 210-8 | | | | | | 5)NOTE: PLEASE PROVIDE REVISED PANEL | | | SCHEDULE SHOWING THE REQ`D DEDICATED | | | CIRCUIT FOR BATH(S). MUST BE #12 AND 20A | | | AS PER 210-11-C-3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|