| 2001-01-08 00:00:00 | SUBMIT SANITARY RISER THAT COMPLIES W/ | | | SPC.WATER CLOSETS AND FIXTURE BRANCHES | | | ARE NOT PERMITTED ON WET VENTS PER | | | COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1 | | | | | | SIZE THE COLD WATER LINES TO THE LAVS IN | | | THE WOMEN'S R.R.COMPLY W/SPC SEC.607. | | | | | | A MIN.OF 29" IS REQUIRED UNDER THE LAV. | | | FROM FINISH FLOOR TO BOTTOM OF APRON PER | | | FACBC SEC.4.19.2. | | | | | | TOILET PAPER DISPENSER SHALL BE LOCATED | | | A MIN.OF 19"TO CENTER PER FACBC 4.16.6 |
|