Plan Review Notes
Plan Review Notes For Permit 00051623
Permit Number 00051623
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT SANITARY RISER THAT COMPLIES W/
 SPC.WATER CLOSETS AND FIXTURE BRANCHES
 ARE NOT PERMITTED ON WET VENTS PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1
  
 SIZE THE COLD WATER LINES TO THE LAVS IN
 THE WOMEN'S R.R.COMPLY W/SPC SEC.607.
  
 A MIN.OF 29" IS REQUIRED UNDER THE LAV.
 FROM FINISH FLOOR TO BOTTOM OF APRON PER
 FACBC SEC.4.19.2.
  
 TOILET PAPER DISPENSER SHALL BE LOCATED
 A MIN.OF 19"TO CENTER PER FACBC 4.16.6