| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT A REVISED LOAD | | | CALCULATION IN CLUDING ALL CONTIUOUS | | | LOADS AT 125%. (LIGHTING ETC.) PLEASE | | | INCLUDE TRACK LIGHTINGFOR IT`S SEPAR- | | | -ATE LOAD CALCULATION PER 220-12-B | | | | | | 2)NOTE: PLEASE SHOW FIGURES FOR SQ.FT | | | PER 220 OF THE NEC. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|