| Plan Review Notes For Permit 00051555 |
| Permit Number |
00051555 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ACCEPTED/CORRECTED BY REVISION7/13/00* | | | 1. SCU-5 SHOWS AS SOURCE OF O/A AND COND | | | ITIONED AIR FOR SPACE SHOW LOCATION AND | | | CONECTION TO DUCTS IN SPACE | | | 2. HPU-1 SHOWS 140 CFM OF OUTSIDE AIR. | | | PROVIDE DETAILS OF O/A CONNECTION TO HPU | | | 3. SHOW EXISTING DUCT LOCATION SOURCE OF | | | CONDITIONED AIR FOR DISTRIBUTION EX: | | | M2.1 SHOWS 15" ROUND DUCT WHERE DOES IT | | | COME FROM? | | | M2.2 SHOWS 3 DUCTS 18" ROUND,17" ROUND, | | | AND A 14" ROUND. WHERE DO THEY COME FROM | | | 4. PROVIDE DUCT AND INSULATION SPECIFI- | | | CATIONS FOR AIR DISTRIBUTION COMPONENTS. | | | 5. PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2 | | | | | | INSUFFICIENT INFORMATION PROVIDED FOR | | | REVIEW. PROVIDE ABOVE INFORMATION AND | | | RESUBMIT |
|