Plan Review Notes
Plan Review Notes For Permit 00051555
Permit Number 00051555
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00ACCEPTED/CORRECTED BY REVISION7/13/00*
 1. SCU-5 SHOWS AS SOURCE OF O/A AND COND
 ITIONED AIR FOR SPACE SHOW LOCATION AND
 CONECTION TO DUCTS IN SPACE
 2. HPU-1 SHOWS 140 CFM OF OUTSIDE AIR.
 PROVIDE DETAILS OF O/A CONNECTION TO HPU
 3. SHOW EXISTING DUCT LOCATION SOURCE OF
 CONDITIONED AIR FOR DISTRIBUTION EX:
 M2.1 SHOWS 15" ROUND DUCT WHERE DOES IT
 COME FROM?
 M2.2 SHOWS 3 DUCTS 18" ROUND,17" ROUND,
 AND A 14" ROUND. WHERE DO THEY COME FROM
 4. PROVIDE DUCT AND INSULATION SPECIFI-
 CATIONS FOR AIR DISTRIBUTION COMPONENTS.
 5. PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2
  
 INSUFFICIENT INFORMATION PROVIDED FOR
 REVIEW. PROVIDE ABOVE INFORMATION AND
 RESUBMIT