| Plan Review Notes For Permit 00051555 |
| Permit Number |
00051555 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | `#`S ON PLANS INCLUDE ALL RECEPT. CIR.`S | | | AND LIGHITNG. 215-5 | | | | | | 2)NOTE: PLEASE SHOW LIGHTING LOADS FIG- | | | -URED AT 125% FOR CONTINUOUS LOAD. | | | PLEASE SHOW IN CLACULATION. | | | | | | 3)NOTE: PANEL EDP SHOWS FEED TO PANEL | | | 'ELP'? NOT SHOWN ON LINE DIAGRAM. | | | | | | EEEETE: PLEASE NOTE THAT AIC RATING OF | | | PANEL 'H5B' IS SHOWN AT 14,000? PLEASE | | | CALRIFY THIS AS A STANDARD RATING. | | | | | | 5)NOTE: PLEASE CHECKLINE DIAGRAM | | | | | | FOR WIRE SIZING. MIGHT BE A TYPE-O FOR | | | MAINS? YOU SHOW #10, PLEASE CHANGE TO | | | 1/0. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 | | | DEWEY PALMER ELECTRICAL PLAN REVIEW |
|