| Plan Review Notes For Permit 00051545 |
| Permit Number |
00051545 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING OF | | | EQUIPMENT MAIN. MAINS/PANELS MUST BE | | | RATEDFOR THE AVAILABLE FAULT CURRENT. | | | 110-9/215-5 THIS IS REQ`D ON ALL PLANS | | | SUBMITTED FOR NEW CONSTRUCTION.!! | | | | | | 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS AND | | | ONE IN COMMON AREA.WIRED INLINE ,120V | | | W/ BATTERY BACK-UP. NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE: PLEASE INCLUDE THE BLDG.STEEL | | | AS PART OF THE GROUNDING ELECTRODE | | | SYSTEM. THIS IS REQ`D PER 250-50/215-5 | | | | | | 4)NOTE: PLEASE NOTE THE REQ`D MEANS OF | | | EGRESS LIGHTING FOR MASTER BEDROOM. | | | 210-70 HOWEVER YOU WANT TO SET IT UP. | | | | | | | | | 5)NOTE; PLEASE SHOW PANEL AS BEING | | | MAIN BRKR. | | | | | | 6)NOTE:PLEASE SUBMIT A PANEL SCHEDULE | | | AND PLEASE INCLUDE THE REQ`D DEDICATED | | | BATH(S) CIRCUIT(S). MUST BE #12 AND 20A | | | PER 210-11-C-3 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATIONN | | | FOR REVIEW.IF THER ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|