Plan Review Notes
Plan Review Notes For Permit 00051545
Permit Number 00051545
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING OF
 EQUIPMENT MAIN. MAINS/PANELS MUST BE
 RATEDFOR THE AVAILABLE FAULT CURRENT.
 110-9/215-5 THIS IS REQ`D ON ALL PLANS
 SUBMITTED FOR NEW CONSTRUCTION.!!
  
 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AND
 ONE IN COMMON AREA.WIRED INLINE ,120V
 W/ BATTERY BACK-UP. NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE INCLUDE THE BLDG.STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM. THIS IS REQ`D PER 250-50/215-5
  
 4)NOTE: PLEASE NOTE THE REQ`D MEANS OF
 EGRESS LIGHTING FOR MASTER BEDROOM.
 210-70 HOWEVER YOU WANT TO SET IT UP.
  
  
 5)NOTE; PLEASE SHOW PANEL AS BEING
 MAIN BRKR.
  
 6)NOTE:PLEASE SUBMIT A PANEL SCHEDULE
 AND PLEASE INCLUDE THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S). MUST BE #12 AND 20A
 PER 210-11-C-3
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATIONN
 FOR REVIEW.IF THER ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372