| Plan Review Notes For Permit 00051520 |
| Permit Number |
00051520 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | | MAINS/PANELS PER 110-9 AND 215-5 | | | | | | 2)NOTE: MISSING SD`S INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS. NFPA-72 2-2.1.1.1 | | | AND ON EACH LEVEL. | | | | | | 3)NOTE: PLEASE LIST THE REQ`D DEDICATED | | | BATH(S) CIRCUIT(S) PER 210-11-C-3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|