| Plan Review Notes For Permit 00051322 |
| Permit Number |
00051322 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT COPY OF JOB SPECIFICATIONS FOR | | | REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | SUBMIT STORM WATER RISER FOR REVIEW.SHOW | | | SQ.FOOT AREA DRAINED BY EACH DRAIN.(SHT. | | | P2.1.1 SHOWS 13,964 SQ.FT.BEING DRAINED | | | FROM 2ND LEVEL BUT SQ.FOOTAGE FOR THE | | | FIRST FLOOR DRAINS HAS NOT BEEN ADDED TO | | | THE CALCULATIONS.COUNTYWIDE AMENDMENTS | | | TO SPC SEC.104.2.1. | | | | | | SHOW PROVISIONS FOR SECONDARY(EMERGENCY) | | | DRAINAGE.COMPLY W/SPC SEC.1109.1,1109.2. | | | SUBMIT CALCULATIONS THAT INCLUDE 1/2 THE | | | AREA OF ANY VERTICAL WALL PER SPC SEC. | | | 1108.3. |
|