| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON |
| | ELEVATION DRAWINGS. BUILDING ADDRESSES |
| | TO COMPLY WITH CITY CODE REQUIREMENTS. |
| | 2) PLEASE CONTACT THE FIRE PREVENTION |
| | BUREAU AT 835-2910 TO REQUEST KNOX-BOX |
| | APPLICATION(S) FOR THE BUILDINGS. |
| | 3) ELEVATORS TO COMPLY WITH ANSI A17.1 |
| | AND THE UNIFORM FIRE CODE FOR ELEVATORS |
| | 4A-47. |
| | 4) INTERIOR FINISHES IN EXITS TO BE |
| | CLASS A OR B. INTERIOR FINISHES IN |
| | OFFICES TO BE CLASS A, B, OR C. |
| | 5) PLEASE PROVIDE FIRE ALARM SYSTEM SHOP |
| | DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN |
| | ON DRAWINGS. CUT SHEETS REQUIRED ON |
| | ALL DEVICES PLANNED FOR USE. |
| | 6) FIRE ALARM SYSTEM AND FIRE SPRINKLER |
| | SYSTEM TO BE MONITORED BY A UL LISTED |
| | CENTRAL STATION APPROVED BY THE FIRE |
| | RESCUE DEPARTMENT. |
| | 7) EXIT DOORS 113 AND 116 WHEN OPENED |
| | ARE NOT TO INTERFERE WITH ONE ANOTHER. |
| | 8) EXIT DOORS WHEN OPENED ARE NOT TO |
| | PROJECT MORE THAN SEVEN INCHES INTO |
| | A REQUIRED EXIT CORRIDOR. |
| | 9) ALL STAIRS TO COMPLY WITH NEW STAIRS |
| | PER NFPA 101, THE LIFE SAFETY CODE, |
| | 1985 EDITION. |
| | APPROVED PROVISO: |