| Plan Review Notes For Permit 00051299 |
| Permit Number |
00051299 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | WATER SUPPLY CONTROL FOR H.W.SHALL | | | COMPLY W/SPC SEC.610.4.1. | | | | | | A SHUT OFF VALVE IS REQD.ON THE C.W. | | | SUPPLY TO THE WATER HEATER PER SPC SEC. | | | 501.6. | | | | | | PLANS SHOW ISLAND VENT BUT IS NOT SHOWN | | | ON THE SANITARY RISER.CLARIFY. | | | | | | GREASE RECOVERY UNITS ARE NOT PERMITTED | | | FOR USE PER CITY OF WEST PALM BEACH ORD. | | | DISCHARGE SHALL BE TO GREASE TRAP. | | | MINIMUM SIZE SHALL BE 750 GALS.AND SHALL | | | BE APPROVED BY CITY OF WEST PALM BEACH | | | UTILITIES.CONTACT R.COMPO AT | | | 561-835-7423.SUBMIT APPROVAL FORM FROM | | | UTILITIES. | | | | | | SUBMIT DETAIL OF GREASE INTERCEPTOR. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | DETAIL 3/P2.1 SHOWS 3"DRAIN AND SANITARY | | | RISER SHOWS 2". | | | | | | INSPECTION REQD.FROM DEPT.OF AGRICULTURE | | | NOT DBR. |
|