2001-01-08 00:00:00WATER SUPPLY CONTROL FOR H.W.SHALL
 COMPLY W/SPC SEC.610.4.1.
  
 A SHUT OFF VALVE IS REQD.ON THE C.W.
 SUPPLY TO THE WATER HEATER PER SPC SEC.
 501.6.
  
 PLANS SHOW ISLAND VENT BUT IS NOT SHOWN
 ON THE SANITARY RISER.CLARIFY.
  
 GREASE RECOVERY UNITS ARE NOT PERMITTED
 FOR USE PER CITY OF WEST PALM BEACH ORD.
 DISCHARGE SHALL BE TO GREASE TRAP.
 MINIMUM SIZE SHALL BE 750 GALS.AND SHALL
 BE APPROVED BY CITY OF WEST PALM BEACH
 UTILITIES.CONTACT R.COMPO AT
 561-835-7423.SUBMIT APPROVAL FORM FROM
 UTILITIES.
  
 SUBMIT DETAIL OF GREASE INTERCEPTOR.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 DETAIL 3/P2.1 SHOWS 3"DRAIN AND SANITARY
 RISER SHOWS 2".
  
 INSPECTION REQD.FROM DEPT.OF AGRICULTURE
 NOT DBR.