| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | THE MINIMUM NUMBER OF REQD.SANITARY | | | FACILITIES SHALL COMPLY W/TABLE 407 OF | | | SPC.SEE SEC.407.1.3.FOR ALLOWED DEDUCT- | | | IBLE AREAS.SUBMIT CORRECT OCCUPANT LOAD. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7.SUPPLY FIXED LADDER OR | | | RELOCATE EWH TO FLOOR. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY SPC | | | SEC.610.4.. | | | | | | SEE ATTACHED FOR PROPER ISLAND VENT. | | | COUNTYWIDE AMENDMENTS TO SPC. 103.7. | | | | | | CLARIFY TYPE OF COOKING OPERATIONS BEING | | | DONE IN THE SPACE. GREASE RECOVERY UNIT | | | IS NOT APPROVED FOR USE PER CITY ORD. | | | DISCHARGE SHALL BE TO A GREASE TRAP. | | | | | | PLANS SHALL BE ROUTED TO DEPT.OF | | | BUSINESS AND PROFESSIONAL REGULATION FOR | | | REVIEW AND APPROVAL PRIOR TO BEING | | | REVIEWED BY THIS DEPARTMENT.SPC SEC. | | | 101.4.7. |
|