Plan Review Notes
Plan Review Notes For Permit 00051299
Permit Number 00051299
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00THE MINIMUM NUMBER OF REQD.SANITARY
 FACILITIES SHALL COMPLY W/TABLE 407 OF
 SPC.SEE SEC.407.1.3.FOR ALLOWED DEDUCT-
 IBLE AREAS.SUBMIT CORRECT OCCUPANT LOAD.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER OR
 RELOCATE EWH TO FLOOR.
  
 WATER SUPPLY CONTROL SHALL COMPLY SPC
 SEC.610.4..
  
 SEE ATTACHED FOR PROPER ISLAND VENT.
 COUNTYWIDE AMENDMENTS TO SPC. 103.7.
  
 CLARIFY TYPE OF COOKING OPERATIONS BEING
 DONE IN THE SPACE. GREASE RECOVERY UNIT
 IS NOT APPROVED FOR USE PER CITY ORD.
 DISCHARGE SHALL BE TO A GREASE TRAP.
  
 PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS AND PROFESSIONAL REGULATION FOR
 REVIEW AND APPROVAL PRIOR TO BEING
 REVIEWED BY THIS DEPARTMENT.SPC SEC.
 101.4.7.